Thermodynamics tells us how much heat must move. 热力学告诉我们必须传递多少热量。
Heat transfer tells us how fast it moves, and so how big the insulation, the exchanger or the heat sink must be. 传热学告诉我们热量传递得有多快,从而确定保温层、换热器或散热器需要多大。
We follow the cooling loop once more - its warm pipes, the parts it quenches, the exchanger that cools its water and the electronics that drive its pump. 我们再来跟踪一次冷却回路:温热的管道、被淬火的零件、冷却回路中水的换热器,以及驱动水泵的电子设备。
Every problem starts with a resistance network. 每个问题都从热阻网络入手。
Heat leaves the sixty-degree water through four resistances in series - the inside film, the steel, the insulation and the outside air film. 热量从 60 度的水中散出,依次经过四个串联热阻:内侧流体膜、钢管、保温层和外侧空气膜。
The insulation alone is two point oh seven of the two point two nine kelvin per watt, so it takes almost all the temperature drop. 总热阻为 2.29 K/W,其中保温层就占了 2.07 K/W,所以几乎全部温降都发生在保温层上。
The loss is seventeen and a half watts per metre, against one hundred and ten for the bare pipe. 每米热损失为 17.5 W,而裸管为 110 W。
For the pump-room wall, add the five resistances - inside film, brick, wool, plaster, outside film. 对于泵房墙壁,把五个热阻相加:内侧流体膜、砖、棉、灰泥和外侧流体膜。
The total is point one four four kelvin per watt, so twenty-seven degrees drives one hundred and eighty-eight watts. 总热阻为 0.144 K/W,因此 27 度的温差会产生 188 W 的传热量。
The fifty millimetres of wool carry three quarters of the drop. 50 mm 厚的棉层承担了四分之三的温降。
On a thin pipe insulation can even increase the loss, but only below the critical radius, four millimetres here. 对于细管,保温层甚至可能增加热损失,但只有在半径小于临界半径时才会发生,这里临界半径为 4 mm。
A quenched part cools fast at first and slowly at the end, exponentially. 淬火零件开始冷却得快,最后冷却得慢,温度呈指数变化。
For a ten-millimetre ball in oil the Biot number is tiny, so the ball has one temperature inside and the time constant is twelve seconds. 对于油中直径为 10 mm 的球,毕奥数很小,所以球内部温度均匀,时间常数为 12 秒。
For the thirty-millimetre shaft in water the Biot number is about one, and the centre lags well behind the surface. 对于水中直径为 30 mm 的轴,毕奥数约为 1,中心温度的变化明显落后于表面。
With a Biot number of one, we use the one-term cylinder solution. 毕奥数为 1 时,我们采用圆柱体的单项近似解。
The table gives zeta one point two seven eight and C one point two one five; the centre reaches three hundred degrees after fifteen point six seconds, when the surface is near two hundred. 查表得到 ζ 为 1.278,C 为 1.215;15.6 秒后中心达到 300 度,此时表面温度接近 200 度。
The lumped model would claim ten seconds and miss the hundred-kelvin difference across the shaft. 集总参数模型会给出 10 秒的结果,而且无法反映轴内 100 K 的温差。
At the wall the air is still, so heat must cross a thin layer by conduction. 在壁面处空气静止,因此热量必须通过一个薄层以热传导的方式传递。
Near the leading edge the layer is thin and h is large; downstream it thickens and h falls with the square root of distance. 靠近前缘时,薄层很薄,h 很大;沿下游方向,薄层逐渐变厚,h 随距离的平方根增大而减小。
For air at four metres per second over a hundred-and-fifty-millimetre plate, the laminar correlation gives an average h of twenty watts per square metre kelvin. 空气以 4 m/s 的速度流过 150 mm 长的平板时,层流关联式给出的平均 h 为 20 W/(m²·K)。
Inside the pipe the loop water moves at three point three metres per second, a Reynolds number of four hundred thousand - fully turbulent. 在管内,回路中的水以 3.3 m/s 的速度流动,雷诺数为 400000,属于充分湍流。
The Dittus-Boelter correlation is valid here, and gives a Nusselt number of twelve hundred and sixty-eight, so h is about ten thousand. 这里可以使用 Dittus-Boelter 关联式,得到努塞尔数为 1268,因此 h 约为 10000。
That is five hundred times the air value, and why the inside film hardly mattered. 这是空气侧数值的 500 倍,也说明了为什么内侧流体膜的影响很小。
Radiation fits the same network idea. 辐射也符合相同的网络思路。
Each surface has a resistance that grows as its emissivity falls, and each pair a space resistance set by the view factor. 每个表面都有一个热阻,发射率越低,这个热阻越大;每对表面之间还有一个由角系数决定的空间热阻。
Between two oven plates at six hundred and three hundred kelvin the flux is four thousand six hundred watts per square metre. 两块炉板的温度分别为 600 K 和 300 K,板间热流密度为 4600 W/m²。
A thin polished shield adds thirty-nine units of resistance and cuts it to one hundred and seventy. 一块薄的抛光遮热板使热阻增加 39 个单位,并将热流密度降至 170 W/m²。
Now add radiation to the bare pipe. 现在把辐射加入裸管的计算。
At sixty degrees with emissivity point eight, the radiation coefficient is five and a half, beside ten for convection. 温度为 60 度、发射率为 0.8 时,辐射换热系数为 5.5,对流换热系数为 10。
The true loss is one hundred and seventy watts per metre, and sixty-one of them are radiation. 实际热损失为每米 170 W,其中 61 W 是辐射损失。
Insulated, the pipe loses eighteen, so the insulation saves eighty-nine percent. 加上保温层后,管道每米损失 18 W,因此保温层减少了 89% 的热损失。
The loop sends two kilograms per second at forty degrees and needs it back at thirty - eighty-four kilowatts. 回路以 2 kg/s 的流量输送 40 度的水,需要水以 30 度返回,所需换热量为 84 kW。
In counterflow the temperature difference stays between thirteen and ten kelvin along the whole exchanger, a log mean of eleven point six, so two point nine square metres is enough. 逆流时,整个换热器内的温差保持在 13 到 10 K 之间,对数平均温差为 11.6 K,所以 2.9 m² 的面积就够了。
Parallel flow starts at twenty and ends at three, and needs a quarter more area. 并流时温差从 20 K 降至 3 K,需要的面积多四分之一。
Buy a three-square-metre unit and rate it with the effectiveness method. 选购一台面积为 3 m² 的换热器,用效能法计算它的性能。
Clean, it delivers eighty-five kilowatts, just enough. 清洁时,它的换热功率为 85 kW,刚好够用。
After a year of scale the fouling resistance drops U to sixteen hundred and sixty-seven, and the duty falls to sixty-seven kilowatts. 结垢一年后,污垢热阻使 U 降至 1667,换热功率降至 67 kW。
Sizing for the fouled coefficient needs four point three square metres. 按结垢后的传热系数选型,需要 4.3 m² 的面积。
The drive loses one hundred and seventy watts in its power module, and the junction must stay below one hundred and twenty-five degrees with forty-degree air. 驱动装置的功率模块损耗 170 W,在空气温度为 40 度时,结温必须保持在 125 度以下。
That allows a sink resistance of point three five. 由此允许的散热器热阻为 0.35。
Twenty aluminium fins with four-metre-per-second air give point two, so the junction runs at ninety-nine degrees - a margin of twenty-six kelvin. 20 片铝翅片配合 4 m/s 的空气流速,可达到 0.2,因此结温为 99 度,留有 26 K 的余量。
The report closes the heat balance and states the margins. 报告核算了热量平衡,并说明了各项余量。
The weakest assumption is h, taken from a flat-plate correlation for flow between fins. 最不可靠的假设是 h,它取自用于翅片间流动的平板关联式。
If it is a quarter lower, the junction reaches one hundred and ten degrees - still safe. 如果它低四分之一,结温将达到 110 度,仍然安全。
Radiation is ignored, which is conservative. 计算忽略了辐射,这是保守的做法。
A fan failure is not covered, so the drive needs a thermal trip. 计算没有考虑风扇故障,因此驱动装置需要热保护跳闸。
Answer from memory first - the wall resistance, the pipe losses with and without radiation, the two quench times, the air and water heat transfer coefficients, the shielded flux, the exchanger areas clean and fouled, and the junction temperature. 先凭记忆回答:墙壁热阻、考虑和不考虑辐射时的管道热损失、两种淬火时间、空气和水的传热系数、使用遮热板后的热流密度、清洁和结垢时所需的换热器面积,以及结温。
Then recompute any you missed, starting from the resistance network. 然后从热阻网络入手,重新计算没答出来的项目。